- Standard power to rack at 3.5kVA with scalable options to 5kVA
- Single power feed of 4.15MVA in a N+2 configuration is provided into the building
- Four static 750kVA (3,000 total kVA); 3+1 configuration
- Two 2.5MVA diesel-powered generators fuelled to provide 80 hrs at full load
- Battery capacity at 15 minutes at full load
- Two to four independent power circuits per cabinet from the resilient banks of UPS on a (N+1) configuration
- Redundant N+1 cooling as 2 chiller systems with 4 risers
- Maximum external ambient temperatures of 24˚C and 50% humidity
- Hot aisle/cold aisle zone design
- Four cooling towers
- Over 450 mm raised floor throughout
- 24/7 central monitoring for all HVAC and building systems
- Multiple bandwidth & IP connectivity options
- Low monthly cross connect fees & choice of managed IT services inside or outside our facilities
- Diverse external and internal fiber routes (POE & building risers), all supported with DSR-MDF-IDF high performance cabling
- Peering with Telehouse America’s International Internet Exchanges allows you to interconnect to multiple transit providers versus connecting individually
- Both NYIIX and LAIIX are based on Brocade carrier class and high speed platform. Public and/or private peering via VLAN services is available. Route servers are available at both locations.
- Gas suppression system ensures no damage to customer equipment
- Smoke alarms with pre-action sprinklers
- State-of-the-art leak sensors in place
- Rooftop antenna access
- 24/7 onsite Facility Engineering, Technical Support & Customer Assistance Centre
- CCTV surveillance installed throughout internal and external perimeters
- Secured & monitored single-person point entry and physical 24/7 security personnel on-site
- 24/7 authorized customer personnel access via regularly updated access lists with photo identification
- Biometric security confirmation system throughout the facility
- Separate access card required for the use of elevators to access customer colocation floor
- Strict security processes are in place to ensure delivery and loading of goods are secure
- Over 450mm (18 inch) raised floor throughout
- 2,700mm (8.85 ft) above raised floor
- Maximum floor load of 700kg/sqm
- Overhead power and communications cable route
- Current PUE level at 1.69
- Customer staging rooms available with storage space
- Access to rooftop antenna available